MCB, RCCB or RCBO? Choosing and Replacing Circuit Breakers
Share
When a breaker fails or a distribution board is extended, the replacement has to match more than the amp rating. MCBs, RCCBs and RCBOs protect against different faults, and each one carries ratings that must suit the circuit. This guide helps M&E contractors, building maintenance teams and purchasers order the right device and avoid nuisance tripping or under-protection.
What each device does
| Device | Protects against | Typical standard | Common use |
|---|---|---|---|
| MCB (miniature circuit breaker) | Overload and short circuit | IEC 60898-1 | Final circuits for lighting, power and equipment |
| RCCB (residual current circuit breaker) | Earth leakage only; no overload protection | IEC 61008 | Protecting a group of circuits, always with MCBs downstream or upstream |
| RCBO (residual current breaker with overcurrent protection) | Overload, short circuit and earth leakage in one device | IEC 61009 | Individual circuits where you do not want one fault to trip several circuits |
The key point: an RCCB on its own does not protect the cable from overload. It must be used with suitably rated MCBs. An RCBO does both jobs for one circuit.
Ratings to match on an MCB or RCBO
Rated current (In)
Common values are 6A, 10A, 16A, 20A, 32A, 40A and 63A. The rating is chosen to protect the cable, so never increase it to stop a breaker tripping. Persistent tripping usually means an overloaded circuit or a fault that needs investigation.
Tripping curve
- Type B: trips at 3–5 times rated current. Suited to lighting and general power with low inrush.
- Type C: trips at 5–10 times rated current. The usual choice for commercial and light industrial circuits with motors, LED drivers or transformers that draw inrush current.
- Type D: trips at 10–20 times rated current. For high-inrush loads such as large motors, welding sets and X-ray equipment.
Replace like with like unless the designer or your Licensed Electrical Worker specifies otherwise. Replacing a Type C breaker with a Type B on an LED lighting circuit is a common cause of nuisance tripping at switch-on.
Breaking capacity
Breaking capacity, shown as 6000 or 10000 in a box on the device (6 kA or 10 kA), is the maximum fault current the breaker can safely interrupt. It must be at least the prospective fault current at that point in the installation. Boards close to the main incoming supply may need a higher breaking capacity than a small sub-board. When in doubt, match the existing device or check the design.
Number of poles
Check whether you need single pole (SP), single pole and neutral (SP+N), double pole (DP), triple pole (TP) or four pole (4P). Three-phase equipment needs TP or 4P devices.
Ratings to match on an RCCB or RCBO
Sensitivity (IΔn)
- 30 mA: for additional protection of people, used on socket outlets and circuits where people may touch equipment.
- 100 mA or 300 mA: used for equipment and fire protection on larger circuits where 30 mA would cause nuisance trips.
Type
The type describes which leakage current waveforms the device detects. Type AC detects sinusoidal AC leakage only. Type A also detects pulsating DC leakage, which electronic loads such as LED drivers, variable speed drives and some appliances can produce. Type F and Type B cover further waveforms and are specified for some drives, EV chargers and solar inverters. Follow the equipment manufacturer's instructions and the design.
Before you order a replacement
- Photograph the label on the existing device, including brand, model, rating, curve, breaking capacity and poles.
- Check the mounting: most modern devices fit 35 mm DIN rail, but older boards may use plug-in or bolt-on types.
- Confirm busbar compatibility if the board uses pin or fork busbars.
- Check the space available in the board. An RCBO can be wider than an MCB.
- Ask whether the brand offers matching accessories such as shunt trips or auxiliary contacts if you need them.
Electrical installation work in Singapore must be carried out or supervised by an appropriately licensed electrical worker under the Energy Market Authority's licensing framework. The guidance here is to help you specify and order; it is not a substitute for their assessment.
Where to start
Browse circuit breakers and panels and circuit breakers for MCBs, RCCBs and RCBOs, switch-disconnectors and isolators for local isolation, and our wider electrical and wiring range.