IP and IK Ratings for Light Fittings: Carparks, Wet Areas and Outdoor Sites

Two short codes on a light fitting datasheet decide whether it will survive where you install it: the IP rating and the IK rating. Get them wrong and you see water inside diffusers, corroded drivers, cracked covers in carparks and repeat call-outs. Get them right and the fitting simply keeps working.

This guide explains how to read both codes and how to match them to common locations in Singapore buildings, from basement carparks to hotel kitchens and open-air walkways.

What the IP rating tells you

The IP (Ingress Protection) code comes from IEC 60529. It has two digits. The first is protection against solid objects and dust; the second is protection against water. A higher number is better within each digit, but the two digits are tested separately.

First digit: solids and dust

  • 2 – protected against fingers. Typical for indoor ceiling fittings.
  • 4 – protected against objects over 1 mm, such as wires and small tools.
  • 5 – dust protected. Some dust may enter, but not enough to affect operation.
  • 6 – dust tight. No dust ingress.

Second digit: water

  • 4 – splashing water from any direction.
  • 5 – low-pressure water jets.
  • 6 – powerful water jets.
  • 7 – temporary immersion (tested at up to 1 m).
  • 8 – continuous immersion, under conditions stated by the manufacturer.
  • 9K – high-pressure, high-temperature wash-down.

One point that catches buyers out: a higher water digit does not automatically include the lower ones. An IP67 fitting is tested for immersion, not necessarily for powerful jets. If a fitting must handle both hosing and occasional flooding, look for a dual marking such as IP66/IP67.

What the IK rating tells you

The IK code comes from IEC 62262 and describes resistance to mechanical impact, measured in joules. It matters wherever fittings can be hit by vehicles, trolleys, ladders, balls or vandals.

IK code Impact energy Typical use
IK06 1 J Indoor areas out of reach
IK07 2 J Corridors and back-of-house
IK08 5 J Carparks, loading bays, stairwells
IK09 10 J Sports halls, public areas at reach height
IK10 20 J Vandal-prone and high-traffic public areas

The IK rating applies to the whole enclosure as tested. A polycarbonate diffuser and an aluminium body may both be part of the rating, so replacement covers should match the original material.

Matching ratings to locations

These are practical starting points, not regulatory minimums. Always check the project specification and the consultant's requirements first.

  • Offices, meeting rooms, hotel guest corridors – IP20 to IP40 is usually enough. Impact rating rarely matters.
  • Toilets and shower areas – IP44 or higher near wet zones; IP65 where fittings may be sprayed during cleaning.
  • Commercial kitchens and food factories – IP65 or IP66 so fittings can be wiped or hosed down. Ask about gasket material and whether the diffuser is shatter-resistant.
  • Basement and multi-storey carparks – IP65 with IK08 or higher. Condensation, dust and vehicle contact all apply.
  • Outdoor walkways, facades and covered linkways – IP65 minimum for Singapore rain; IP66 where fittings face direct driving rain or are cleaned with pressure washers.
  • Wash-down plant, marine decks and ports – IP66/IP67 with corrosion-resistant housings and stainless fixings.
  • Hazardous areas – IP and IK are not enough on their own; the fitting must be certified for the zone.

Things the rating does not cover

An IP rating is a laboratory test on a new, correctly assembled fitting. On site, several things can undo it:

  • Cable glands – an IP66 fitting with the wrong gland size, or an unused entry left open, is no longer IP66.
  • Gaskets – rubber seals age in heat and UV. Check them whenever a fitting is opened, and replace any that are flattened or cracked.
  • Mounting – drilling extra holes in a housing voids the rating.
  • Corrosion – IP says nothing about salt air. For coastal and marine sites, ask about housing material, coating and fixing grade separately.
  • UV yellowing – some polycarbonate diffusers discolour outdoors over time. Ask whether the diffuser is UV-stabilised.

What to ask your supplier

  1. The full IP and IK codes for the complete fitting, not just the driver or LED module.
  2. The test standard referenced (IEC 60529 and IEC 62262) and, for project submissions, the test report or certificate.
  3. Gland sizes and cable diameter range supported.
  4. Operating temperature range, especially for fittings in plant rooms or under metal roofs.
  5. Housing and diffuser material, and whether replacement gaskets and covers are available.

You can browse weatherproof and robust options in our lighting fixtures range, including weatherproof emergency lights for carparks and outdoor escape routes. For petrochemical, marine and other classified areas, see our explosion proof lighting.

Need help matching a fitting?

If you are replacing a failed fitting, the IP and IK codes are usually printed on the label inside the cover or on the housing. Send us the part number, a photo or the old label and a real person will quote within 24 hours. For technical questions about ratings, materials or project submissions, email cs@delight.com.sg.