CRI, CCT and UGR: Reading a Light Fitting Spec Sheet for Offices and Hotels

Office and hotel fit-out specs often list a row of numbers next to each light fitting: 4000K, Ra>80, UGR<19, 3,600 lm, 36 W. Two fittings that look the same in a catalogue can feel very different once installed. This guide explains what each figure means, which ones matter for offices, meeting rooms, lobbies and guest areas, and what to check before you approve a substitute.

The five numbers on a lighting spec sheet

Figure What it measures Typical office or hospitality value
CCT (K) Colour temperature, from warm (lower K) to cool (higher K) 2700K–3000K for guest rooms and F&B; 4000K for offices; 5000K–6500K for back-of-house and workshops
CRI (Ra) How naturally colours look under the light, out of 100 Ra 80 minimum for work areas; Ra 90 for retail, food display and premium interiors
UGR Unified Glare Rating: how much discomfort glare the fitting causes 19 or lower for desks and screens; 22–25 acceptable for corridors and stores
Lumens (lm) Total light output Depends on room size and target lux
Efficacy (lm/W) Light output per watt of power Higher means lower running cost for the same light

Colour temperature (CCT): match the mood and the task

CCT is the number most people notice first. Warm white (2700K–3000K) feels relaxed and suits hotel rooms, restaurants and lounges. Neutral white (4000K) is the usual choice for open offices, classrooms and clinics because it feels bright without looking clinical. Cool white and daylight (5000K–6500K) suit car parks, plant rooms, warehouses and workshops.

The common mistake is mixing CCTs in one space. If you are replacing a few failed downlights in a lobby, match the existing CCT exactly. A 3000K fitting next to a 4000K fitting is obvious to guests and tenants.

CRI (Ra): how true colours look

CRI compares how colours appear under the fitting against a reference light source. Ra 80 is the normal minimum for indoor work areas. For spaces where colour matters, such as retail, food display, F&B counters, hotel bathrooms and design studios, ask for Ra 90 or above.

Some spec sheets also show R9, the score for saturated red. A low R9 makes skin tones and food look dull. If a supplier quotes Ra 90, it is reasonable to ask what the R9 value is.

UGR: the glare figure that tenants complain about

UGR estimates discomfort glare from a fitting in a standard room layout. Lower is better. For offices with computer screens, the common target is UGR 19 or lower, which is the figure used in the European workplace lighting standard EN 12464-1 for writing, reading and computer work. Singapore's own code of practice for lighting of workplaces, SS 531, is also worth checking if your consultant has specified it.

Fittings achieve low UGR with microprismatic diffusers, deep louvres or recessed optics. A plain opal panel light is cheaper but often has a higher UGR. If a substitute panel is offered at a lower price, check its UGR before you approve it for a desk area.

Points to check on a UGR claim

  • Is the value stated for the specific model and diffuser, not just the product family?
  • Is it stated as UGR<19 or a range such as 19–22? A range is not the same as a guaranteed low figure.
  • Is there a photometric file (IES or LDT) your consultant can use to check the layout?

Lumens, watts and efficacy

Wattage tells you power consumption, not brightness. Compare fittings by lumens and by lumens per watt. A 36 W panel at 120 lm/W gives more light than a 40 W panel at 90 lm/W. When replacing older fluorescent fittings with LED, use the lumen figure to match light levels rather than the old wattage.

Flicker and the driver

Cheap LED fittings can flicker in ways you do not see directly but can feel as eye strain, and that show up as banding on phone cameras and CCTV. Flicker performance depends mostly on the driver. Ask whether the driver is flicker-free or low-ripple, and whether it is dimmable if the room uses dimming. If you are replacing a failed driver, match the output current or voltage, power and dimming type. Our LED drivers and power supplies range covers common replacement types.

A short checklist before you approve a fitting or substitute

  1. CCT matches the existing fittings in the same space.
  2. CRI is Ra 80 or higher, and Ra 90 where colour matters.
  3. UGR is 19 or lower for desk and screen areas, stated for that exact model.
  4. Lumen output meets the lighting design, not just the wattage.
  5. Driver is flicker-free or low-ripple, and dimmable if needed.
  6. Cut-out size, mounting type and ceiling depth match the existing installation.
  7. Datasheet, photometric file and warranty terms are provided.

Where to start