Choosing Fire Extinguishers for Offices, Kitchens and Plant Rooms
Share
Every building needs fire extinguishers, but not every extinguisher suits every room. A dry powder unit in a server room leaves a corrosive mess; a water extinguisher near a switchboard is dangerous; a CO2 unit will not deal with a deep-fat fryer fire. For facility managers looking after offices, hotels, schools and mixed-use buildings, choosing the right type for each area is a basic but important decision.
This guide covers fire classes, extinguisher types and a simple monthly check routine. It does not replace your building's fire safety requirements, the advice of your Fire Safety Manager where one is appointed, or the servicing contractor's recommendations.
Fire classes
Extinguishers are labelled with the classes of fire they are tested against:
- Class A – ordinary solid materials: paper, wood, fabric, cardboard, many plastics.
- Class B – flammable liquids: petrol, diesel, solvents, paints.
- Class C – flammable gases, such as LPG.
- Class D – burning metals. Needs specialist extinguishers.
- Class F – cooking oils and fats in commercial kitchens.
Electrical equipment is not a separate class in this system, but the label will indicate whether the extinguisher is suitable for use on live electrical equipment.
Extinguisher types compared
| Type | Suitable for | Not suitable for | Typical location |
|---|---|---|---|
| Water | Class A | Live electrical, liquids, cooking oil | Corridors, offices with paper storage |
| Foam | Class A and B | Cooking oil fires; check label for electrical use | Workshops, stores with liquids |
| Dry powder (ABC) | Class A, B and C; many rated for electrical | Enclosed spaces where powder affects visibility and breathing; sensitive equipment | Carparks, outdoor plant, vehicles, loading bays |
| Carbon dioxide (CO2) | Class B and electrical equipment | Class A deep-seated fires; cooking oil fires | Switch rooms, server rooms, offices with IT equipment |
| Wet chemical | Class F, and usually Class A | Live electrical | Commercial kitchens |
Matching extinguishers to areas
Offices and meeting rooms
Mainly Class A materials plus IT equipment. Many buildings pair a water or foam unit with a CO2 unit near clusters of electrical equipment.
Pantries and commercial kitchens
Wet chemical extinguishers are designed for cooking oil fires. A fire blanket is useful for small pan fires in pantries. Never use water on burning oil.
Switch rooms, MSB rooms and server rooms
CO2 is the usual choice because it leaves no residue. CO2 displaces oxygen, so staff should leave a small enclosed room after discharge and ventilate it before re-entry.
Carparks, loading bays and outdoor plant
Dry powder works well on mixed risks and outdoors, where the powder disperses and residue matters less.
Workshops and chemical stores
Foam or powder, depending on the liquids stored. Check the SDS of stored chemicals for any specific firefighting advice.
A monthly visual check routine
Between professional servicing visits, a quick monthly walk-round by the facility team helps catch problems early:
- The extinguisher is in its designated place, mounted or on a stand, and not blocked by furniture, boxes or trolleys.
- The signage above or beside it is visible.
- The pressure gauge needle, where fitted, is in the green zone.
- The safety pin and tamper seal are intact.
- The hose or horn is not cracked, kinked or blocked.
- The body shows no dents, rust or leaks.
- The operating instructions on the label are legible.
- The service tag shows a current inspection date.
Record each check. Any unit that has been discharged, even partly, or fails a check should be taken out of service and replaced or sent for servicing. Formal servicing and testing should be done by a qualified servicing company at the intervals your fire safety requirements and the manufacturer specify.
Do not forget first aid and exit lighting
The same walk-round is a good time to check that first aid boxes are stocked and in date, and that exit signs and emergency lights are lit and undamaged. Workplaces in Singapore also have first aid obligations under the WSH (First-Aid) Regulations, so keep box contents and records up to date.
What to ask when buying
- Extinguisher type, capacity and fire ratings on the label.
- Whether the model is suitable for use on electrical equipment.
- Wall brackets or stands, and matching signage.
- Any certification or listing your building's fire safety requirements call for.