MEANWELL DRH Series Rail Mount Power Supply
MEANWELL DRH Series Rail Mount Power Supply
SKU SKU:DRH-120-24
Kongsi
Ciri-ciri :
- Perlindungan: Litar pintas / Lebihan beban / Lebih voltan / Lebih suhu
- Penyejukan melalui perolakan udara bebas
- Litar pengehad arus malar terbina dalam
- Boleh dipasang pada rel DIN TS-35/7.5 atau 15
- EN61000-6-2(EN50082-2} tahap imuniti industri
- 100% ujian pembakaran beban penuh
- Kekerapan pensuisan tetap pada 70KHz
Spesifikasi:
MODEL |
DRH-120-24 |
DRH-120-48 |
|
PENGELUARAN |
VOLTAN DC |
24V |
48V |
BERKADAR SEMASA |
5A |
2.5A |
|
Julat SEMASA |
0 ~ 5A |
0 ~2.5A |
|
KUASA BERKATA |
120W |
120W |
|
RIPPLE & NOISE (maks.) Nota.2 |
80mVp-p |
80mVp-p |
|
VOLTAN ADJ. RANGKAIAN |
24 ~ 28V |
48 ~ 55V |
|
TOLERANSI VOLTAN Catatan.3 |
±1.0% |
±1.0% |
|
PERATURAN TALIAN |
±0.5% |
±0.5% |
|
PERATURAN BEBAN |
±0.5% |
±0.5% |
|
SETUP, BANGKIT, TAHAN MASA |
1700ms, 120ms, 16ms/400VAC 1000ms, 120ms, 30ms/500VAC pada beban penuh |
||
INPUT |
Julat VOLTAN |
340 ~ 550VAC 480 ~ 780VDC |
|
JARAK FREKUENSI |
47 ~ 63Hz |
||
KECEKAPAN (Jenis) |
85% |
86% |
|
ARUS AC |
0.65A/400VAC 0.6A/500VAC |
||
ARUS MASUK (maks.) |
MULA SEJUK 50A |
||
ARUS KEBOCORAN |
<3.5mA / 530VAC |
||
PERLINDUNGAN |
LEBIHAN BEBAN |
105 ~ 160% kuasa keluaran undian |
|
Jenis perlindungan : Pengehadan arus malar, pulih secara automatik selepas keadaan kerosakan dialihkan |
|||
LEBIH VOLTAN |
30 ~ 36V |
59 ~ 66V |
|
Jenis perlindungan : Matikan voltan o/p, hidupkan semula untuk pulih |
|||
MELEBIHI SUHU |
Jenis perlindungan : Matikan voltan o/p, pulih secara automatik selepas suhu turun |
||
PERSEKITARAN |
TEMPAT BEKERJA. |
-20 ~ +60 ℃ (Rujuk "Keluk Penurunan") |
|
KELEMBAPAN BEKERJA |
20 ~ 90% RH tidak pemeluwapan |
||
SUHU PENYIMPANAN, KELEMBAPAN |
-40 ~ +85℃, 10 ~ 95% RH |
||
TEMP. KOEFISIEN |
±0.03%/℃ (0 ~ 50℃) |
||
GETARAN |
Komponen: 10 ~ 500Hz, 2G 10min./1kitaran, 60min. setiap satu di sepanjang paksi X, Y, Z; Klip pelekap: Pematuhan kepada IEC60068-2-6 |
||
KESELAMATAN & EMC (Nota 4) |
STANDARD KESELAMATAN |
UL60950-1, EAC TP TC 004 diluluskan, IEC60950-1 CB diluluskan oleh SIQ |
|
TAHAN VOLTAN |
I/PO/P:3KVAC I/P-FG:2.0KVAC O/P-FG:0.5KVAC |
||
RINTANGAN PENGASINGAN |
I/PO/P, I/P-FG, O/P-FG:100M Ohm / 500VDC / 25℃/ 70% RH |
||
EMISI EMC |
Pematuhan kepada EN55011 (CISPR11), EN55032 (CISPR32), EN61204-3 Kelas B, EAC TP TC 020 |
||
KEIMUNITI EMC |
Pematuhan kepada EN61000-4-2,3,4,5,6,8,11, EN61204-3, EN61000-6-2 (EN50082-2), tahap industri berat, kriteria A, EAC TP TC 020 |
||
LAIN-LAIN |
MTBF |
178.7Khrs min. MIL-HDBK-217F (25℃) |
|
DIMENSI |
65.5*125.2*100mm (W*H*D) |
||
PEMBUNGKUSAN |
0.75Kg; 20pcs/16Kg/1.29CUFT |
||
CATATAN |
1. Semua parameter yang TIDAK dinyatakan secara khusus diukur pada input 400VAC, beban berkadar dan 25℃ suhu ambien. 2. Riak & hingar diukur pada lebar jalur 20MHz dengan menggunakan wayar pasangan terpiuh 12" yang ditamatkan dengan kapasitor selari 0.1uf & 47uf. 3. Toleransi : termasuk toleransi persediaan, peraturan talian dan peraturan beban. 4. Bekalan kuasa dianggap sebagai komponen yang akan dipasang ke dalam peralatan akhir. Peralatan akhir mesti disahkan semula bahawa ia masih memenuhi arahan EMC. 5. Penurunan suhu ambien 3.5℃/1000m dengan model tanpa kipas dan 5℃/1000m dengan model kipas untuk ketinggian operasi lebih tinggi daripada 2000m(6500ft). |