R1
RS Pro 2 x 58W Hazardous Area Light Fitting
RS Pro 2 x 58W Hazardous Area Light Fitting
SKU SKU:5396980
สต็อกสินค้าเหลือน้อย: เหลือ 2 ชิ้น
แบ่งปัน
Technical data sheets
*Check stock before ordering. Lead time 4 working days.*
Petrel Zone 2 Anti-corrosive
A highly competitive zone two fluorescent luminaire, for use in both internal and external hazardous area applications. Featuring a moulded GRP body and polycarbonate diffuser this fluorescent luminaire is classed as “unrestricted breathing” equipment, which means it doesn’t need any routine testing during annual maintenance inspections. This zone 2 luminaire has a simple design, with easy access to all parts. Lamps can be changed easily, by releasing the stainless steel diffuser clips and removing the diffuser. Three hour emergency versions are fitted with integral batteries and charging unit.
Robust, lightweight and slimline construction for use with bi-pin fluorescent lamps
GRP body with polycarbonate diffuser and stainless steel clips
Unrestricted breathing enclosure
Electronic HF ballast for longer tube life and lower running costs
2 X M20 cable entries (1 plugged) with 3 wire and earth terminals for 2.5mm cable
Specifications
Attribute | Value |
Type | Anti-Corrosive |
Zone Classification | 2 |
Temperature Classification | T4 |
Wattage | 2 x 58 W |
Lamp Type | Fluorescent |
Voltage Rating | 240 V ac |
Anti-corrosive | Yes |
Length | 1.62 m |
Width | 170 mm |
Individual Lamp Wattage | 58W |
Number of Lamps | 2 |
Series | XN |
Hazardous Area Certification | ATEX |
Standards Met | EEX nc II 3 GD, EN50021 |