S7
MEANWELL HRPG Series With PFC
MEANWELL HRPG Series With PFC
SKU:HRPG-300-12
ไม่สามารถโหลดความพร้อมในการรับสินค้าด้วยตนเองได้
Delivery
Delivery
Singapore
1-3 work days ( 90% of Shipments)
For items that are stocked outside Singapore, it takes 7 - 14 work days.
International
7-14 work days.
Pick FEDEX at checkout for reliable and Fast Deliveries.
Taxes
Taxes
Singapore
GST Not Applicable - Prices displayed are final prices.
International
As per importering country's Duties and taxes. To be paid to Carrier or Customs Dept. Importer is responsible for Import Duty and Taxes.
แผ่นข้อมูล
แผ่นข้อมูล
cs@delight.com.sg
Tel: +65 6429 8402
Whatsapp: +65 8900 0895
We admit ! For Technical Clarifications, our AI BOT is Quicker than us. Try it !
แบ่งปัน
Features:
- Universal AC input / Full range
- Built-in active PFC function, PF>0.95
- High efficiency up to 89%
- Withstand 300VAC surge input for 5 seconds
- Protections: Short circuit / Overload / Over voltage / Over temperature
- Built-in constant current limiting circuit
- 1U low profile 41mm
- Built-in cooling fan ON-OFF control
- Built-in DC OK signal
- Built-in remote ON-OFF control
- Standby 5V@0.3A
- Built-in remote sense function
- No load power consumption<0.5W (Note.6}
Specification:
|
MODEL |
HRPG-300-3.3 |
HRPG-300-5 |
HRPG-300-7.5 |
HRPG-300-12 |
HRPG-300-15 |
HRPG-300-24 |
HRPG-300-36 |
HRPG-300-48 |
|
|
OUTPUT |
DC VOLTAGE |
3.3V |
5V |
7.5V |
12V |
15V |
24V |
36V |
48V |
|
RATED CURRENT |
60A |
60A |
40A |
27A |
22A |
14A |
9A |
7A |
|
|
CURRENT RANGE |
0 ~ 60A |
0 ~ 60A |
0 ~ 40A |
0 ~ 27A |
0 ~ 22A |
0 ~ 14A |
0 ~ 9A |
0 ~ 7A |
|
|
RATED POWER |
198W |
300W |
300W |
324W |
330W |
336W |
324W |
336W |
|
|
RIPPLE & NOISE (max.) Note.2 |
80mVp-p |
90mVp-p |
100mVp-p |
120mVp-p |
150mVp-p |
150mVp-p |
250mVp-p |
250mVp-p |
|
|
VOLTAGE ADJ. RANGE |
2.8 ~ 3.8V |
4.3 ~ 5.8V |
6.8 ~ 9V |
10.2 ~ 13.8V |
13.5 ~ 18V |
21.6 ~ 28.8V |
28.8 ~ 39.6V |
40.8 ~ 55.2V |
|
|
VOLTAGE TOLERANCE Note.3 |
±2.5% |
±2.0% |
±2.0% |
±1.0% |
±1.0% |
±1.0% |
±1.0% |
±1.0% |
|
|
LINE REGULATION |
±0.5% |
±0.5% |
±0.5% |
±0.3% |
±0.3% |
±0.2% |
±0.2% |
±0.2% |
|
|
LOAD REGULATION |
±1.0% |
±1.0% |
±1.0% |
±0.5% |
±0.5% |
±0.5% |
±0.5% |
±0.5% |
|
|
SETUP, RISE TIME |
1000ms, 50ms/230VAC 2500ms, 50ms/115VAC at full load |
||||||||
|
HOLD UP TIME (Typ.) |
16ms/230VAC 16ms/115VAC at full load |
||||||||
|
INPUT |
VOLTAGE RANGE Note.5 |
85 ~ 264VAC 120 ~ 370VDC |
|||||||
|
FREQUENCY RANGE |
47 ~ 63Hz |
||||||||
|
POWER FACTOR (Typ.) |
PF>0.95/230VAC PF>0.99/115VAC at full load |
||||||||
|
EFFICIENCY (Typ.) |
80% |
82% |
86% |
88% |
88% |
87% |
88% |
89% |
|
|
AC CURRENT (Typ.) |
3.5A/115VAC 1.8A/230VAC |
||||||||
|
INRUSH CURRENT (Typ.) |
35A/115VAC 70A/230VAC |
||||||||
|
LEAKAGE CURRENT |
<1.2mA / 240VAC |
||||||||
|
PROTECTION |
OVERLOAD |
105 ~ 135% rated output power |
|||||||
|
Protection type : Constant current limiting, recovers automatically after fault condition is removed |
|||||||||
|
OVER VOLTAGE |
3.96 ~ 4.62V |
6 ~ 7V |
9.4 ~ 10.9V |
14.4 ~ 16.8V |
18.8 ~ 21.8V |
30 ~ 34.8V |
41.4 ~ 48.6V |
57.6 ~ 67.2V |
|
|
Protection type : Shut down o/p voltage, re-power on to recover |
|||||||||
|
OVER TEMPERATURE |
Shut down o/p voltage, recovers automatically after temperature goes down |
||||||||
|
FUNCTION |
5V STANDBY |
5VSB : 5V@0.3A ; tolerance±5%, ripple : 50mVp-p(max.) |
|||||||
|
DC OK SIGNAL |
PSU turns on : 3.3 ~ 5.6V ; PSU turns off : 0 ~ 1V |
||||||||
|
REMOTE CONTROL |
RC+ / RC-: 4 ~ 10V or open = power on ; 0 ~ 0.8V or short = power off |
||||||||
|
FAN CONTROL (Typ.) |
Load 35±15% or RTH2≧50℃ Fan on |
||||||||
|
ENVIRONMENT |
WORKING TEMP. |
-40 ~ +70℃ (Refer to "Derating Curve") |
|||||||
|
WORKING HUMIDITY |
20 ~ 90% RH non-condensing |
||||||||
|
STORAGE TEMP., HUMIDITY |
-40 ~ +85℃, 10 ~ 95% RH |
||||||||
|
TEMP. COEFFICIENT |
± 0.03%/℃ (0 ~ 50℃) |
||||||||
|
VIBRATION |
10 ~ 500Hz, 5G 10min./1cycle, 60min. each along X, Y, Z axes |
||||||||
|
SAFETY & EMC (Note 4) |
SAFETY STANDARDS |
UL62368-1, TUV EN62368-1, EAC TP TC 004 approved |
|||||||
|
WITHSTAND VOLTAGE |
I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC |
||||||||
|
ISOLATION RESISTANCE |
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25℃/ 70% RH |
||||||||
|
EMC EMISSION |
Compliance to EN55032 (CISPR32) Class B, EN61000-3-2,-3, EAC TP TC 020 |
||||||||
|
EMC IMMUNITY |
Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61000-6-2, heavy industry level, criteria A, EAC TP TC 020 |
||||||||
|
OTHERS |
MTBF |
176K hrs min. MIL-HDBK-217F (25℃) |
|||||||
|
DIMENSION |
199*105*41mm (L*W*H) |
||||||||
|
PACKING |
0.95Kg;15pcs/15.3Kg/0.69CUFT |
||||||||
|
NOTE |
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature. 2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor. 3. Tolerance : includes set up tolerance, line regulation and load regulation. 4. The power supply is considered a component which will be installed into a final equipment. All the EMC tests are been executed by mounting the unit on a 360mm*360mm metal plate with 1mm of thickness. The final equipment must be re-confirmed that it still meets EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies.” (as available on http://www.meanwell.com} 5. Derating may be needed under low input voltages. Please check the derating curve for more details. 6. No load power consumption<0.5W when RC- & RC+ (CN100 pin4,6} 0 ~ 0.8V or short. 7. The ambient temperature derating of 3.5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitude higher than 2000m(6500ft}. |
||||||||