S7
MEANWELL DRH Series Rail Mount Power Supply
MEANWELL DRH Series Rail Mount Power Supply
SKU SKU:DRH-120-24
แบ่งปัน
Features :
- Protections: Short circuit / Overload / Over voltage / Over temperature
- Cooling by free air convection
- Built-in constant current limiting circuit
- Can be installed on DIN rail TS-35/7.5 or 15
- EN61000-6-2(EN50082-2} industrial immunity level
- 100% full load burn-in test
- Fixed switching frequency at 70KHz
Specification:
MODEL |
DRH-120-24 |
DRH-120-48 |
|
OUTPUT |
DC VOLTAGE |
24V |
48V |
RATED CURRENT |
5A |
2.5A |
|
CURRENT RANGE |
0 ~ 5A |
0 ~2.5A |
|
RATED POWER |
120W |
120W |
|
RIPPLE & NOISE (max.) Note.2 |
80mVp-p |
80mVp-p |
|
VOLTAGE ADJ. RANGE |
24 ~ 28V |
48 ~ 55V |
|
VOLTAGE TOLERANCE Note.3 |
±1.0% |
±1.0% |
|
LINE REGULATION |
±0.5% |
±0.5% |
|
LOAD REGULATION |
±0.5% |
±0.5% |
|
SETUP, RISE, HOLD UP TIME |
1700ms, 120ms, 16ms/400VAC 1000ms, 120ms, 30ms/500VAC at full load |
||
INPUT |
VOLTAGE RANGE |
340 ~ 550VAC 480 ~ 780VDC |
|
FREQUENCY RANGE |
47 ~ 63Hz |
||
EFFICIENCY (Typ.) |
85% |
86% |
|
AC CURRENT |
0.65A/400VAC 0.6A/500VAC |
||
INRUSH CURRENT (max.) |
COLD START 50A |
||
LEAKAGE CURRENT |
<3.5mA / 530VAC |
||
PROTECTION |
OVERLOAD |
105 ~ 160% rated output power |
|
Protection type : Constant current limiting, recovers automatically after fault condition is removed |
|||
OVER VOLTAGE |
30 ~ 36V |
59 ~ 66V |
|
Protection type : Shut down o/p voltage, re-power on to recover |
|||
OVER TEMPERATURE |
Protection type : Shut down o/p voltage, recovers automatically after temperature goes down |
||
ENVIRONMENT |
WORKING TEMP. |
-20 ~ +60℃ (Refer to "Derating Curve") |
|
WORKING HUMIDITY |
20 ~ 90% RH non-condensing |
||
STORAGE TEMP., HUMIDITY |
-40 ~ +85℃, 10 ~ 95% RH |
||
TEMP. COEFFICIENT |
±0.03%/℃ (0 ~ 50℃) |
||
VIBRATION |
Component: 10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting clip: Compliance to IEC60068-2-6 |
||
SAFETY & EMC (Note 4) |
SAFETY STANDARDS |
UL60950-1, EAC TP TC 004 approved, IEC60950-1 CB approved by SIQ |
|
WITHSTAND VOLTAGE |
I/P-O/P:3KVAC I/P-FG:2.0KVAC O/P-FG:0.5KVAC |
||
ISOLATION RESISTANCE |
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25℃/ 70% RH |
||
EMC EMISSION |
Compliance to EN55011 (CISPR11), EN55032 (CISPR32), EN61204-3 Class B, EAC TP TC 020 |
||
EMC IMMUNITY |
Compliance to EN61000-4-2,3,4,5,6,8,11, EN61204-3, EN61000-6-2 (EN50082-2), heavy industry level, criteria A, EAC TP TC 020 |
||
OTHERS |
MTBF |
178.7Khrs min. MIL-HDBK-217F (25℃) |
|
DIMENSION |
65.5*125.2*100mm (W*H*D) |
||
PACKING |
0.75Kg; 20pcs/16Kg/1.29CUFT |
||
NOTE |
1. All parameters NOT specially mentioned are measured at 400VAC input, rated load and 25℃ of ambient temperature. 2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor. 3. Tolerance : includes set up tolerance, line regulation and load regulation. 4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives. 5. The ambient temperature derating of 3.5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitude higher than 2000m(6500ft}. |